ESD Conductive Copper Foil Tape 12 mm × 50 m

Item No.: CP-26
Description
Description

Product Overview

A single-sided conductive copper foil tape for the earthing grid of ESD vinyl flooring. The copper carries a conductive acrylic adhesive on one face and stays bare on the other, so strips bond to each other where they cross. Supplied 12 mm wide in 50 m rolls.

Conductive copper foil tape 12 mm x 50 m for ESD flooring earthing

12 mm × 50 m roll, single-sided conductive adhesive.

It does two jobs in a floor build-up. It carries the conductive adhesive layer of the flooring through to the building earth, and at every crossing it carries continuity from one run to the next. Both jobs happen under the floor, after which neither can be inspected without lifting it.

Why the Tape Decides the Reading

When an installed ESD floor fails its handover test, the covering is rarely the cause. The resistance chain runs from the surface, through the wear layer, through the conductive flooring adhesive, into this tape, along the grid, and out to the building earth.

Every joint in that chain is a place where contact can be lost, and the tape is the segment that gets buried first and inspected least. It is also the cheapest part of the system to get right.

The tape is one link, not the whole chain. Resistance measured on the tape is a material value; it is not a prediction of what the finished floor will read. The installed figure depends on the flooring, the conductive adhesive, the grid layout and the earthing together, and is measured on site after installation.

How the Grid Is Laid

Layout follows the flooring manufacturer's installation guide. Typical practice:

Area Layout
Under 50 m² Strip spacing of 0.6–1.0 m, run outward from the building earth connection
Over 50 m² Grid at 6–8 m centres, with roughly 1 m of strip run from the grid to each earthing point
Project specification Where it calls for closer spacing than the above, the specification governs

Because the flooring adhesive is itself conductive, this tape forms a grounding grid rather than a full-area mesh. Full copper coverage is not required — the grid gives the charge a route, the adhesive gives it the connection.

  • Substrate — clean, dry, sound and free of dust, oil, curing compounds and loose material. Prime where the substrate is absorbent.
  • Sequence — lay the tape before the flooring adhesive, and press it down along its full length.
  • Line — straight and flat. Trapped air or a lifted edge breaks continuity.
  • Record — test continuity across the grid and write the readings down before the adhesive goes on.

One Adhesive Face, Two Jobs

The tape is adhesive on one side only, and that is deliberate.

At a crossing, the adhesive face of one strip is pressed onto the bare copper face of the other. The conductive adhesive completes the joint itself, so no solder and no separate connector is needed. A strip that was adhesive on both faces would leave no bare copper to bond to.

Two things break this joint in practice: splicing two runs with ordinary insulating tape, and letting flooring adhesive sit between the two copper faces at a crossing. Both leave a floor that looks continuous and reads open.

Technical Data

Property Value Method
Width 12 mm —
Length per roll 50 m —
Copper foil thickness 0.025 mm —
Total thickness 0.050 mm —
Construction Copper foil, conductive acrylic adhesive on one face, siliconised release paper —
Copper purity ≥ 99.95 % —
Electrical resistance, tape ≤ 0.05 Ω (typical 0.038 Ω) JK2511
Initial tack Steel ball No. 8 ASTM D1000
Holding power ≥ 48 h (typical 50 h) J.DOW
Peel strength 1.1 – 1.2 kN PSPC-7
Service temperature −10 to +120 °C —
Shelf life 6 months at 25 °C / 65 % RH —
Packaging Individually wrapped roll; product name, width, length, lot number and date of manufacture on the label —
Compliance Method Result
EU RoHS (EU) 2015/863 — Pb, Hg, Cd, Cr(VI), PBB, PBDE, DEHP, BBP, DBP, DIBP IEC 62321 series Pass
Halogen content — F, Cl, Br, I EN 14582:2016 Not detected
Do not apply wax, polish or a synthetic floor finish over an ESD floor — these form an insulating film and raise the surface resistance. Clean with a neutral detergent only.

Continuity and Earthing Checks

Continuity is tested across the grid and recorded before the flooring adhesive is applied. Once the covering is down, a fault can still be measured but its cause is no longer visible, and lifting the floor to find it costs more than the tape did.

Connection to the building earth is made by a qualified electrician. The flooring guide typically requires the building earth connection to measure 10–100 Ω. The number of earthing points and the conductor size are set by the project's electrical specification, not by the tape.

What Actually Fails on a Copper Grid

Three failures account for most of them, and none of them is the copper itself.

  • Insulating joins — ordinary tape used to splice two runs leaves an insulating layer in the one place continuity has to cross.
  • Adhesive between copper faces — flooring adhesive is conductive, but a bead sitting between two copper faces at a crossing is a barrier, not a bridge.
  • The earth terminal — one earthing point per room is normal; if that clamp corrodes, or the connection is made to a painted conduit rather than to earth, the whole grid floats and every reading drifts.

None of this shows up at delivery. It shows up at handover, or years later when the floor is re-tested.

Ordering and Delivery

Item Terms
Article number CP-26
Minimum order 20 rolls
Lead time 5–7 days after written confirmation of specification
Price basis FOB Shanghai; other terms on request
Sample Short length of any width on request

The tape is supplied as a roll of 12 mm by 50 m. Quantities for a project usually follow the grid layout rather than the floor area, so the roll count is best calculated from the drawing before ordering.

FAQ

Do I need copper tape if the flooring adhesive is already conductive?

Yes. The adhesive carries charge from the floor covering into the tape; the tape is what gives it a route to earth. Without the grid, a floor that measures correctly as a material still has no path to the building earth and reads open once installed.

How far apart should the strips be?

Under 50 m², strips at 0.6–1.0 m spacing run outward from the earth connection. Over 50 m², a grid at 6–8 m centres with roughly 1 m run to each earthing point. Where the project specification is stricter, it governs.

Can I splice two rolls with ordinary tape?

No. Ordinary tape is an insulator, and it would sit exactly where continuity has to cross. Splice with the conductive adhesive face against bare copper, or plan the layout so the runs join at a crossing.

Why is it adhesive on one side only?

So that crossings can be made without solder. One strip presents adhesive, the other presents bare copper, and the conductive adhesive completes the joint. A tape adhesive on both faces would have nothing bare to bond to at a crossing.

Does the tape have to cover the whole floor?

No. Because the flooring adhesive is conductive, the tape works as a grounding grid rather than a full-area mesh. Covering the whole floor with copper adds cost without improving the reading.

What resistance will my finished floor read?

The tape does not determine that figure. The installed floor is measured as a system, and its resistance depends on the flooring, the conductive adhesive, the grid layout and the quality of the earthing together. The material value for the tape is ≤ 0.05 Ω; the installed figure is measured on site after installation.

Where does this fit with your ESD flooring?

It is the earthing component of the same system. The ESD vinyl tile flooring and ESD vinyl sheet flooring pages describe the full build-up; this tape is laid under either of them. The wider ESD vinyl flooring range is listed separately.