NEXUS ESD sheet is a homogeneous conductive vinyl floor supplied in rolls of 2 metres by 20 or 15 metres, in 2.0 mm and 3.0 mm. It is made in twenty references, YLSD-5501 to YLSD-5522, and is produced in two electrical grades on the same construction.
The roll format is the reason most large ESD areas are specified in sheet rather than tile. A 2-metre roll laid and hot-welded leaves one seam every two metres instead of a joint every 600 mm, and a seam that is welded with conductive rod carries the charge across it. On a 500 m² hall that is the difference between roughly 1,400 joints and 50.
A single welded sheet across a data hall — no tile grid, no joint every 600 mm.
Tile and sheet solve the same problem with different economics. Tile is easier to handle, easier to lift for service access and easier to keep in stock. Sheet wins where the area is large and the continuity matters more than the handling.
| Consideration | Sheet (2 m roll) | Tile (600 × 600) |
|---|---|---|
| Seam density on 500 m² | About 50 linear metres of weld | About 1,400 joints |
| Conductive path across seams | Welded with conductive rod | Welded with conductive rod |
| Subfloor tolerance | Less forgiving; substrate must be flat | Tolerates minor variation |
| Service access to floor boxes | Requires cutting and re-welding | Lift and replace the tile |
| Best fit | Data halls, cleanrooms, production halls | Raised floors, plant rooms, small areas |
Where a project is planned around raised access floor panels, tile is normally the correct answer regardless of area. Where the floor is monolithic and the room is large, sheet removes most of the joints that would otherwise have to be welded and later maintained.
The construction carries conductivity in the body of the material rather than in a coating applied to it. There is no separate copper mesh built into the roll; the conductive network runs through the wear layer and the fibreglass grid below it.

Both grades are made on the same line from the same construction. The difference is the conductive filler loading, and it is fixed when the order is placed — not selected on site.
| Selection point | Static dissipative (SD) | Conductive (EC) |
|---|---|---|
| Resistance band | 1.0 × 10⁶ – 10⁹ Ω | 2.5 × 10⁴ – 10⁶ Ω |
| Discharge rate | Controlled, slower bleed | Faster bleed to earth |
| Typical specification | Electronics assembly, server rooms, laboratories | Component handling, explosive-risk areas, ordnance and solvent stores |
| Material classification | EN 1081 surface resistance | EN 1081 surface resistance |
| Installed floor acceptance | IEC 61340-5-1 — completed floor below 1 × 10⁹ Ω | IEC 61340-5-1 — completed floor below 1 × 10⁹ Ω |
Twenty references, YLSD-5501 to YLSD-5522. The decorative chip runs through the full thickness, so the pattern survives traffic and the surface can be maintained by dry buffing rather than repeated coating.
YLSD-5504 and YLSD-5514 are not part of the current range. Colour reproduction on screen is indicative — physical samples are issued before an order is confirmed, and OEM colour matching is available on request.
Two roll lengths and two thicknesses cover most layouts. The 2-metre width suits corridors and standard bay spacing without a longitudinal waste cut; the length is chosen so that a run finishes on a weld rather than a shortened piece.
| Format | Size | Thickness | Weight |
|---|---|---|---|
| Roll | 2 × 20 m | 2.0 mm | 2,900 g/m² |
| Roll | 2 × 15 m | 2.0 mm | 2,900 g/m² |
| Roll | 2 × 20 m | 3.0 mm | On request |
| Roll | 2 × 15 m | 3.0 mm | On request |
3.0 mm is produced to order. The extra thickness is specified where the substrate is less than perfect, where trolley traffic is heavy, or where the floor has to bridge minor irregularities without telegraphing them through. Both thicknesses carry the same electrical specification.
The sheet only behaves as a conductive floor when the whole build-up is conductive. Laid on a conventional adhesive it reads as an insulator no matter what the material measures, because the bond line breaks the path to earth.
| Property | Standard | Value |
|---|---|---|
| Thickness | EN 428 | 2.0 mm / 3.0 mm |
| Roll size | EN 426 | 2 × 20 m / 2 × 15 m |
| Weight | EN 430 | 2,900 g/m² at 2.0 mm |
| Electrical resistance, SD | EN 1081 | 1.0 × 10⁶ – 10⁹ Ω |
| Electrical resistance, EC | EN 1081 | 2.5 × 10⁴ – 10⁶ Ω |
| Static decay | SJ/T 10694-2006 | Average 0.3 s (input below 100 V) |
| Charge voltage, walking test | SJ/T 10694-2006 | Average 70 V |
| Fire rating | DIN 4102-1 | B1 |
| Combustion behaviour | Vertical burn test | FV-0; after-flame 0.35 s |
| Smoke density | ASTM E-662 | < 450 |
| Abrasion loss | Gravimetric, 1,000 cycles | ≤ 0.020 g/cm² |
| Wear resistance | EN 660-2 (Frick-Taber) | Volume loss 2.0 – 4.0 mm³ (former EN 649 class P) |
| Anti-bacterial | DIN EN ISO 846-A/C | No bacterial growth |
| Castor chair | EN 425 | No effect |
| Residual indentation | EN ISO 24343-1 (ex EN 433) | ≤ 0.10 mm |
| Dimensional stability | EN ISO 23999 (ex EN 434) | ≤ 0.35% |
| Colour fastness | ISO 105-B02 | Grade 6 |
| Chemical resistance | DIN 423 · EN ISO 26987 | Good; specific agents on request |
| Impact sound absorption | ISO 140 · ISO 717 | Approx. 2 dB |
| Slip resistance | DIN EN 16165:2021-12 (prev. DIN 51130) | R9 |
| Thermal conductivity | EN 12667 | 0.03 W/(m·K) |
| Cleanroom classification | ISO 14644-1 | Class 4 |
| Hazardous substances | GB 18586 | Compliant |
| Smoke toxicity | GB/T 20285-2006 | ZA3 |
Values in the table describe the material as supplied. Test reports for the batch are available on request; where a project specification quotes a figure outside this table, confirm it against the report before the floor is tendered.
The format is chosen by the room. Large uninterrupted areas, wet cleaning regimes and rooms where the floor must read as a single plane are the natural fit.


An ESD floor passes on the day it is measured, not on the day it is delivered. The table below separates what is checked in the factory from what has to be checked in the room, because the second is where most failures occur.
| Check | Method | Carried out by | When |
|---|---|---|---|
| Material resistance | EN 1081 on a conditioned sample | Manufacturer | At production, reported per batch |
| Installed resistance | IEC 61340-4-1, point-to-point and point-to-earth | Installer, witnessed by the client | After welding and cleaning, before handover |
| Earth continuity | Copper strip to earth terminal, continuity meter | Electrical contractor | Before the floor is laid |
| Seam continuity | Resistance across a welded seam | Installer | Spot checks during welding |
| Re-test | Same method, same instrument | Facility or contractor | Annually, and after any floor works |
| Item | Terms |
|---|---|
| Minimum order | 500 m² per colour |
| Lead time | 7–10 days after written confirmation of specification |
| Price basis | FOB Shanghai; other terms on request |
| Sample | A4 sample of any reference, with test report |
| Colour matching | OEM matching available against a submitted sample |
Quantities are calculated on covered area plus a cutting allowance for the room perimeter and for pattern alignment where a directional lay is specified. Mixed orders are packed by reference so that rolls arrive separated by colour rather than in one undifferentiated load.
The deciding question is whether the floor is monolithic or made of removable panels. On a raised access floor, tile is normally correct because you will need to lift panels for cabling. On a solid slab in a large room, sheet removes hundreds of welded joints and is easier to keep continuous for cleaning. A hybrid is common: sheet across the main hall, tile in the plant room.
Yes. The sheet carries a conductive plane through its body and fibreglass grid, but that plane still has to reach earth. The copper strip laid on the substrate and bonded to the earth terminal is what provides the route. Without it the floor has no reference potential, and readings drift from one end of the room to the other.
SD reads 1.0 × 10⁶ to 10⁹ Ω and bleeds charge at a controlled rate; it is the usual choice for electronics assembly and server rooms. EC reads 2.5 × 10⁴ to 10⁶ Ω and discharges faster; it is specified where the risk is ignition rather than component damage. The grade is fixed at order — it cannot be changed on site.
Yes. Seams are hot-welded with conductive rod and the weld is trimmed flush, giving a continuous surface that can be wet-cleaned. The weld also carries the conductive path across the joint, which is why the rod must be the conductive type and not a standard PVC rod.
You will not know from the delivery document — you will know from the handover reading. Record the installed resistance and the earth continuity value at handover, then re-measure annually with the same instrument and method. If the number moves, the change tells you whether the cause is contamination, a failed seam or a deteriorated earth connection.
No. The chip runs through the full thickness of the sheet, so wear removes material but does not remove the pattern, and there is no printed film to expose. This is also why the surface can be maintained by dry buffing rather than repeated coating — a coating would sit on top of the conductive layer and interfere with it.
The slab must be flat and dry. Sheet is thinner and less forgiving than tile, so hollows and ridges show through. Levelling compound, moisture testing and primer are part of the ESD scope — if they are skipped, the finished floor will look uneven and the adhesive coverage will be inconsistent, which shows up later as a resistance fault rather than as a cosmetic one.