ESD Vinyl Sheet Flooring NEXUS YLSD-5501 - YLSD-5522

Item No.: YLSD-5501 - YLSD-5522
Description
Description

Product Overview

NEXUS ESD sheet is a homogeneous conductive vinyl floor supplied in rolls of 2 metres by 20 or 15 metres, in 2.0 mm and 3.0 mm. It is made in twenty references, YLSD-5501 to YLSD-5522, and is produced in two electrical grades on the same construction.

The roll format is the reason most large ESD areas are specified in sheet rather than tile. A 2-metre roll laid and hot-welded leaves one seam every two metres instead of a joint every 600 mm, and a seam that is welded with conductive rod carries the charge across it. On a 500 m² hall that is the difference between roughly 1,400 joints and 50.

ESD vinyl sheet installed across a server room floor

A single welded sheet across a data hall — no tile grid, no joint every 600 mm.

Why Sheet, Not Tile

Tile and sheet solve the same problem with different economics. Tile is easier to handle, easier to lift for service access and easier to keep in stock. Sheet wins where the area is large and the continuity matters more than the handling.

Consideration Sheet (2 m roll) Tile (600 × 600)
Seam density on 500 m² About 50 linear metres of weld About 1,400 joints
Conductive path across seams Welded with conductive rod Welded with conductive rod
Subfloor tolerance Less forgiving; substrate must be flat Tolerates minor variation
Service access to floor boxes Requires cutting and re-welding Lift and replace the tile
Best fit Data halls, cleanrooms, production halls Raised floors, plant rooms, small areas

Where a project is planned around raised access floor panels, tile is normally the correct answer regardless of area. Where the floor is monolithic and the room is large, sheet removes most of the joints that would otherwise have to be welded and later maintained.

How the Four Layers Work

The construction carries conductivity in the body of the material rather than in a coating applied to it. There is no separate copper mesh built into the roll; the conductive network runs through the wear layer and the fibreglass grid below it.

Four-layer construction of the ESD vinyl sheet
  • Static-control wear layer — the surface that people and trolleys actually contact, formulated so charge leaves through the body rather than accumulating on top.
  • Through-colour wear layer — the full thickness carries the decorative chip, so the pattern cannot be walked off and there is no printed film to expose.
  • Fibreglass grid — stabilises the sheet dimensionally and provides the continuous conductive plane across the roll width.
  • Dense backing — the layer that bonds to the conductive adhesive and completes the path to the substrate grid.
A surface-applied anti-static treatment can be worn through or stripped by a strong cleaner. This sheet has no separate treatment layer to lose — the property belongs to the body of the material. Resistance can still drift with contamination, humidity and the condition of the earthing, which is why the installed floor is tested rather than assumed.

Two Electrical Grades, One Construction

Both grades are made on the same line from the same construction. The difference is the conductive filler loading, and it is fixed when the order is placed — not selected on site.

Static dissipative (SD)
1.0 × 10⁶ – 10⁹ Ω
EN 1081
Conductive (EC)
2.5 × 10⁴ – 10⁶ Ω
EN 1081
Selection point Static dissipative (SD) Conductive (EC)
Resistance band 1.0 × 10⁶ – 10⁹ Ω 2.5 × 10⁴ – 10⁶ Ω
Discharge rate Controlled, slower bleed Faster bleed to earth
Typical specification Electronics assembly, server rooms, laboratories Component handling, explosive-risk areas, ordnance and solvent stores
Material classification EN 1081 surface resistance EN 1081 surface resistance
Installed floor acceptance IEC 61340-5-1 — completed floor below 1 × 10⁹ Ω IEC 61340-5-1 — completed floor below 1 × 10⁹ Ω
Resistance values describe the floor covering as a material. The resistance of the installed floor also depends on the conductive adhesive, the copper strip layout and the quality of the earth connection, and is verified on site after installation. A material that reads correctly in the laboratory can still fail at handover if the earthing is incomplete.

Colour Range

Twenty references, YLSD-5501 to YLSD-5522. The decorative chip runs through the full thickness, so the pattern survives traffic and the surface can be maintained by dry buffing rather than repeated coating.

YLSD-5501
YLSD-5501
YLSD-5502
YLSD-5502
YLSD-5503
YLSD-5503
YLSD-5505
YLSD-5505
YLSD-5506
YLSD-5506
YLSD-5507
YLSD-5507
YLSD-5508
YLSD-5508
YLSD-5509
YLSD-5509
YLSD-5510
YLSD-5510
YLSD-5511
YLSD-5511
YLSD-5512
YLSD-5512
YLSD-5513
YLSD-5513
YLSD-5515
YLSD-5515
YLSD-5516
YLSD-5516
YLSD-5517
YLSD-5517
YLSD-5518
YLSD-5518
YLSD-5519
YLSD-5519
YLSD-5520
YLSD-5520
YLSD-5521
YLSD-5521
YLSD-5522
YLSD-5522

YLSD-5504 and YLSD-5514 are not part of the current range. Colour reproduction on screen is indicative — physical samples are issued before an order is confirmed, and OEM colour matching is available on request.

Roll Sizes and Thickness

Two roll lengths and two thicknesses cover most layouts. The 2-metre width suits corridors and standard bay spacing without a longitudinal waste cut; the length is chosen so that a run finishes on a weld rather than a shortened piece.

Format Size Thickness Weight
Roll 2 × 20 m 2.0 mm 2,900 g/m²
Roll 2 × 15 m 2.0 mm 2,900 g/m²
Roll 2 × 20 m 3.0 mm On request
Roll 2 × 15 m 3.0 mm On request

3.0 mm is produced to order. The extra thickness is specified where the substrate is less than perfect, where trolley traffic is heavy, or where the floor has to bridge minor irregularities without telegraphing them through. Both thicknesses carry the same electrical specification.

Installation System

The sheet only behaves as a conductive floor when the whole build-up is conductive. Laid on a conventional adhesive it reads as an insulator no matter what the material measures, because the bond line breaks the path to earth.

  • Substrate preparation — the slab must be flat and dry. Sheet telegraphs substrate variation that tile would absorb, so levelling is part of the ESD scope, not an optional extra.
  • Primer — seals the substrate so the adhesive cures evenly and the conductive filler stays in contact with the slab.
  • Copper strip — laid across the substrate and bonded to the earth terminal, forming the reference plane the adhesive connects to.
  • Conductive adhesive — carbon-loaded, applied by notched trowel at the coverage stated on the pail.
  • Conductive welding rod — seams hot-welded so continuity crosses the joint rather than stopping at it. This is the step that most often separates a working floor from a failing one.
The sheet carries its own conductive network through the body and the fibreglass grid, which is why no separate copper mesh is required inside the roll. The copper strip still has to be laid on the substrate and earthed — the roll provides the plane, the installation provides the route to earth.

Technical Data

Property Standard Value
Thickness EN 428 2.0 mm / 3.0 mm
Roll size EN 426 2 × 20 m / 2 × 15 m
Weight EN 430 2,900 g/m² at 2.0 mm
Electrical resistance, SD EN 1081 1.0 × 10⁶ – 10⁹ Ω
Electrical resistance, EC EN 1081 2.5 × 10⁴ – 10⁶ Ω
Static decay SJ/T 10694-2006 Average 0.3 s (input below 100 V)
Charge voltage, walking test SJ/T 10694-2006 Average 70 V
Fire rating DIN 4102-1 B1
Combustion behaviour Vertical burn test FV-0; after-flame 0.35 s
Smoke density ASTM E-662 < 450
Abrasion loss Gravimetric, 1,000 cycles ≤ 0.020 g/cm²
Wear resistance EN 660-2 (Frick-Taber) Volume loss 2.0 – 4.0 mm³ (former EN 649 class P)
Anti-bacterial DIN EN ISO 846-A/C No bacterial growth
Castor chair EN 425 No effect
Residual indentation EN ISO 24343-1 (ex EN 433) ≤ 0.10 mm
Dimensional stability EN ISO 23999 (ex EN 434) ≤ 0.35%
Colour fastness ISO 105-B02 Grade 6
Chemical resistance DIN 423 · EN ISO 26987 Good; specific agents on request
Impact sound absorption ISO 140 · ISO 717 Approx. 2 dB
Slip resistance DIN EN 16165:2021-12 (prev. DIN 51130) R9
Thermal conductivity EN 12667 0.03 W/(m·K)
Cleanroom classification ISO 14644-1 Class 4
Hazardous substances GB 18586 Compliant
Smoke toxicity GB/T 20285-2006 ZA3

Values in the table describe the material as supplied. Test reports for the batch are available on request; where a project specification quotes a figure outside this table, confirm it against the report before the floor is tendered.

Measured at 10 V for surface and point-to-point resistance; resistance to earth measured at 100 V for 1 MΩ–100 GΩ and at 500 V above 100 GΩ. Reported values are geometric means of the readings taken across the area (one reading per 2 m²), after conditioning at 20–25 °C and 40–60 % RH for 24 h.

Where It Is Specified

The format is chosen by the room. Large uninterrupted areas, wet cleaning regimes and rooms where the floor must read as a single plane are the natural fit.

ESD sheet in a computer roomESD sheet in an electronics production workshop
  • Data halls and server rooms — perimeter aisles, plant areas and cold-aisle floors where a tile grid would interrupt airflow sealing.
  • Electronics production — SMT lines, assembly bays and test areas where the floor is one layer of the static programme.
  • Cleanrooms — ISO Class 4 compatible; welded seams keep the surface continuous for cleaning.
  • Laboratories and pharmacies — where solvent or powder makes ignition a credible risk.
  • Operating theatres and clinical areas — where a discharge near equipment is unacceptable and the floor must be cleanable.

How Resistance Is Verified

An ESD floor passes on the day it is measured, not on the day it is delivered. The table below separates what is checked in the factory from what has to be checked in the room, because the second is where most failures occur.

Check Method Carried out by When
Material resistance EN 1081 on a conditioned sample Manufacturer At production, reported per batch
Installed resistance IEC 61340-4-1, point-to-point and point-to-earth Installer, witnessed by the client After welding and cleaning, before handover
Earth continuity Copper strip to earth terminal, continuity meter Electrical contractor Before the floor is laid
Seam continuity Resistance across a welded seam Installer Spot checks during welding
Re-test Same method, same instrument Facility or contractor Annually, and after any floor works
The adhesive, the copper strip and the earth terminal are installed by different trades. When a floor reads high after handover, the cause is more often the earth connection or a missed seam weld than the sheet itself. Recording the earth continuity reading before the floor goes down is what makes that diagnosis possible.

Ordering and Delivery

Item Terms
Minimum order 500 m² per colour
Lead time 7–10 days after written confirmation of specification
Price basis FOB Shanghai; other terms on request
Sample A4 sample of any reference, with test report
Colour matching OEM matching available against a submitted sample

Quantities are calculated on covered area plus a cutting allowance for the room perimeter and for pattern alignment where a directional lay is specified. Mixed orders are packed by reference so that rolls arrive separated by colour rather than in one undifferentiated load.

FAQ

Should I use sheet or tile in my room?

The deciding question is whether the floor is monolithic or made of removable panels. On a raised access floor, tile is normally correct because you will need to lift panels for cabling. On a solid slab in a large room, sheet removes hundreds of welded joints and is easier to keep continuous for cleaning. A hybrid is common: sheet across the main hall, tile in the plant room.

Is copper strip still needed if the sheet is conductive?

Yes. The sheet carries a conductive plane through its body and fibreglass grid, but that plane still has to reach earth. The copper strip laid on the substrate and bonded to the earth terminal is what provides the route. Without it the floor has no reference potential, and readings drift from one end of the room to the other.

What is the difference between the SD and EC grades?

SD reads 1.0 × 10⁶ to 10⁹ Ω and bleeds charge at a controlled rate; it is the usual choice for electronics assembly and server rooms. EC reads 2.5 × 10⁴ to 10⁶ Ω and discharges faster; it is specified where the risk is ignition rather than component damage. The grade is fixed at order — it cannot be changed on site.

Can the seams be made watertight?

Yes. Seams are hot-welded with conductive rod and the weld is trimmed flush, giving a continuous surface that can be wet-cleaned. The weld also carries the conductive path across the joint, which is why the rod must be the conductive type and not a standard PVC rod.

How do I know the floor will still pass in a year?

You will not know from the delivery document — you will know from the handover reading. Record the installed resistance and the earth continuity value at handover, then re-measure annually with the same instrument and method. If the number moves, the change tells you whether the cause is contamination, a failed seam or a deteriorated earth connection.

Does the pattern wear off under traffic?

No. The chip runs through the full thickness of the sheet, so wear removes material but does not remove the pattern, and there is no printed film to expose. This is also why the surface can be maintained by dry buffing rather than repeated coating — a coating would sit on top of the conductive layer and interfere with it.

What substrate preparation does sheet require?

The slab must be flat and dry. Sheet is thinner and less forgiving than tile, so hollows and ridges show through. Levelling compound, moisture testing and primer are part of the ESD scope — if they are skipped, the finished floor will look uneven and the adhesive coverage will be inconsistent, which shows up later as a resistance fault rather than as a cosmetic one.