NEXUS ESD tile is a homogeneous polyvinyl chloride floor covering that carries a permanent conductive path through its full thickness. It is produced in 600 × 600 mm and 900 × 900 mm tiles at 2.0 mm and 3.0 mm, in eighteen references from ESD-6601 to ESD-6618, and is supplied in two electrical grades on one construction.
The material is specified where a static discharge would damage product or endanger people: electronics assembly, semiconductor and PCB handling, server rooms, laboratories, and operating theatres. It is normally ordered by flooring contractors, cleanroom engineering companies, and distributors serving those sectors.

A person walking across an insulating floor generates a charge of several thousand volts. When that person touches a circuit board, the charge leaves the body in a fraction of a second. The component sees the discharge, not the walk.
A conductive floor does not prevent the charge from forming. It gives the charge a continuous path to earth, so the potential never accumulates to a level that can damage a device. The floor becomes part of the earthing system rather than an obstacle to it.
This is why an ESD floor is assessed on resistance and on decay time together. A floor that reads correctly on a meter but does not drain quickly still allows charge to build during movement.
The tile is made in a conductive grade and a dissipative grade. Both share the same wear layer, the same decorative chip through the body, and the same installation system. The grade is selected against the sensitivity of the equipment standing on the floor.
| Selection point | Conductive | Dissipative |
|---|---|---|
| Static generation | Below 100 V | Below 300 V |
| Static decay, 5,000 V to zero | Under 0.01 s | Under 0.2 s |
| Typical use | Component handling, electronics assembly | Explosive-risk areas, server halls |
| Test conditions | EN 1815, conductive footwear, 20% RH | EN 1815, conductive footwear, 20% RH |
Where the specification calls for one grade and the other is supplied, the floor may still read within tolerance on a meter while failing the process requirement. The grade is fixed at order, not at installation.
Eighteen references, ESD-6601 to ESD-6618. The decorative chip runs through the full thickness of the tile, so the pattern does not wear away with traffic and the surface can be maintained by dry buffing rather than coating.
Colour reproduction on screen is indicative. Physical samples are supplied before an order is confirmed.
Two tile sizes and two thicknesses cover most layouts without a cut pattern. The 900 × 900 mm tile reduces the number of seams across large halls; the 600 × 600 mm tile suits rooms with service penetrations, raised-floor grids and irregular partitions.
| Format | Size | Thickness | Weight | EN ISO 10874 |
|---|---|---|---|---|
| Tile | 600 × 600 mm | 2.0 mm | 3.2 kg/m² | Class 34/43 |
| Tile | 900 × 900 mm | 2.0 mm | 3.2 kg/m² | Class 34/43 |
| Tile | 600 × 600 mm | 3.0 mm | 5.4 kg/m² | Class 34/43 |
| Tile | 900 × 900 mm | 3.0 mm | 5.4 kg/m² | Class 34/43 |
Class 34/43 covers heavy traffic in commercial premises and light industrial use, which is the classification most electronics and healthcare interiors are specified against.
The floor only works as a system. Tile laid on a conventional adhesive reads as an insulator no matter what the tile itself measures, because the bond line breaks the path to earth. Four components are supplied together for that reason.

The copper grid is earthed at one point per room. That single point gives the finished floor one stable potential across the whole area instead of a set of local readings that drift against each other.
The foil runs across the joints rather than stopping at them, so tiles on either side of a seam stay on the same conductive path.
Open time on the adhesive is 10–20 minutes. Seams are welded no earlier than 24 hours after the tile is laid, and the floor is not handed over until resistance has been measured across the completed area.
| Property | Standard | Conductive | Dissipative |
|---|---|---|---|
| CEN classification | EN ISO 10874 (prev. EN 685) | Class 34/43 | Class 34/43 |
| Thickness | EN 428 | 2.0 / 3.0 mm | 2.0 / 3.0 mm |
| Size | EN 427 | 600 × 600 / 900 × 900 mm | 600 × 600 / 900 × 900 mm |
| Weight | EN 430 | 3.2 kg/m² (2.0 mm) · 5.4 kg/m² (3.0 mm) | 3.2 kg/m² (2.0 mm) · 5.4 kg/m² (3.0 mm) |
| Electrical resistance | EN 1081 (ex DIN 51953) · ASTM F150 | 2.5 × 10⁴ – 10⁶ Ω | 10⁶ – 10⁸ Ω |
| Static generation | EN 1815 | Below 100 V, conductive footwear, 20% RH | Below 300 V, conductive footwear, 20% RH |
| Static decay | FTM 101 · Method 4046 | 5,000 V to zero in under 0.01 s at 15% RH | 5,000 V to zero in under 0.2 s at 15% RH |
| Thermal resistance | EN 12667 (prev. DIN 52612) | 0.00618 m²K/W (2.0 mm) | 0.00618 m²K/W (2.0 mm) |
| Thermal conductivity | EN 12667 (prev. DIN 52612) | 0.309 W/m·K | 0.309 W/m·K |
| Fire resistance | DIN 4102 · ÖNORM B3810 | B1, B1Q1 | B1, B1Q1 |
| Critical radiant flux | ASTM E-648 / NFPA 253 | Above 1.08 W/cm², Class 1 | Above 1.08 W/cm², Class 1 |
| Flame spread | ASTM E-84 (UL 723) | Below 75 | Below 75 |
| Smoke density | ASTM E-662 | Below 450 | Below 450 |
| Abrasion resistance | ASTM D-1044, CS-10F wheel, 500 g / 1,000 g | Gauge loss 0.40 / 0.80 / 1.20 / 1.60 % at 2,500 / 5,000 / 7,500 / 10,000 cycles | Gauge loss 0.40 / 0.80 / 1.20 / 1.60 % at 2,500 / 5,000 / 7,500 / 10,000 cycles |
| Resistance to wear | EN 660-1 / DIN 51963 | M | M |
| Residual indentation | EN ISO 24343-1 (ex EN 433) | 0.03 mm (2.0 mm) · 0.04 mm (3.0 mm) | 0.03 mm (2.0 mm) · 0.04 mm (3.0 mm) |
| Dimensional stability | EN ISO 23999 (ex EN 434) | ≤ 0.10% | ≤ 0.10% |
| Effect of castor chair | EN 425 | No damage | No damage |
| Colour fastness | ISO 105-B02 | At least 6 | At least 6 |
| Resistance to chemicals | DIN 423 / DIN 51958 | Excellent; specific agents on request | Excellent; specific agents on request |
| Impact sound absorption | ISO 140 · ISO 717 | Approx. 2 dB | Approx. 2 dB |
| Healthcare facilities | NFPA 99 | Conforms at time of installation | Conforms at time of installation |
The material is chosen by function of the room, not by traffic alone. The same tile is used across all of the following, with the grade and thickness selected per area.
The conductive path is only as continuous as its weakest component, so the sundries are matched to the tile rather than sourced separately.
Tiles are packed by reference and by size, so a mixed order arrives separated by decor rather than in a single pallet load. Quantities are calculated on covered area plus a cutting allowance for the room perimeter.
A sample card of the full eighteen references is issued before an order is placed. Production is scheduled against the confirmed reference list, and the resistance test report for the batch is available on request.
The grade follows the sensitivity of what the room handles, not the size of the room. Where a discharge of a few hundred volts would damage the product, the conductive grade is specified. Where the risk is ignition of a vapour or powder, the dissipative grade is usually specified. Both grades are made on the same construction, so the choice does not change the appearance or the installation method.
No. A conventional adhesive insulates the tile from the substrate and the finished floor will read as an insulator on a resistance meter regardless of the tile's own specification. The conductive adhesive and the copper grid are part of the product, not an optional upgrade.
It is necessary wherever the floor must be earthed to a defined point, which covers virtually all ESD specifications. The grid is bonded to earth at one point per room. On a small room the run is short; on a large hall the grid is laid in strips across the whole area so that no point of the floor is far from a conductive path.
The chip runs through the full thickness of the tile. Wear removes material but does not remove the pattern, and there is no printed layer to expose. This is also why the surface can be maintained by dry buffing instead of repeated coating.
2.0 mm is the standard for most commercial and electronics interiors. 3.0 mm is used where the substrate is less than perfect, where castor traffic is heavy, or where the floor must bridge minor irregularities without showing them. Both thicknesses carry the same electrical specification.
Yes, and it should be. Resistance is measured across the completed floor after welding, not on a loose sample. The reading is affected by the adhesive, the grid, the seams and the moisture content of the substrate, so measuring the installed floor is the only result that reflects the finished installation.